UPS Battery Configuration calculation method:

(UPS capacity <VA>) x power factor X backup time/start voltage =ah< >

which

The start-up voltage can be consulted by the manufacturer. Typically 384V or 240V (single-phase or three-phase).

The number of batteries per group is calculated according to the starting voltage and the voltage of each battery. That is, a group of one-hour batteries = starting voltage (such as 384V)/single cell volt (e.g. 12V)

You can generally calculate a group of one-hour battery ah number,

such as 6KVA ups, single-phase, power factor 0.7, then 6000*0.7/240=17.5 is a group of one-hour battery ah number.

If the total is 24AH, that is 24/17.5=1.37 hours.

Similarly, if you need 2.17 hours, the total battery ah number equals 2.17 * 17.5 = 38AH.

Contact Us

The content source of this page is from Internet, which doesn't represent Alibaba Cloud's opinion; products and services mentioned on that page don't have any relationship with Alibaba Cloud. If the content of the page makes you feel confusing, please write us an email, we will handle the problem within 5 days after receiving your email.

If you find any instances of plagiarism from the community, please send an email to: info-contact@alibabacloud.com and provide relevant evidence. A staff member will contact you within 5 working days.

A Free Trial That Lets You Build Big!

Start building with 50+ products and up to 12 months usage for Elastic Compute Service

  • Sales Support

    1 on 1 presale consultation

  • After-Sales Support

    24/7 Technical Support 6 Free Tickets per Quarter Faster Response

  • Alibaba Cloud offers highly flexible support services tailored to meet your exact needs.