Preface: Today to collate information, found a few years ago I encountered a patrol fault, so take out to do record, to avoid data loss. first, warning phenomenon:
1: 6509 main engine SYSTEM light Red
2: 6509 chassis back line integrated Board light Red
Second, the device hardware indicator level analysis:
Cisco official for the main engine,the system lights up Several cases of the description:
Green-all Chassis environmental monitors is reporting OK.
Orange-the power supply has failed or the power supply fan hasfailed.
Red-incompatible power Supplies is installed. (power supply Exception)
– The redundant clock has failed. (redundant clock exceptions)
– One VTT1 module has failed or the VTT module temperature minorthreshold have been exceeded2. (Piece VTT Module exception, or VTT module temperature abnormality)
– VTT modules fail or the VTT module temperature major Thresholdhas been exceeded3. (Two pieces VTT module exception, or temperature abnormality)
– The temperature of the Supervisor engine major threshold has beenexceeded(engine temperature anomaly)
Three, equipment system alarm Level analysis:
6509 has the following alarms:
Environmental alarms:
System minor alarm on operating VTT count (raised 18w1d ago)
System minor alarm on VTT 2 OK (raised18w1d ago)
Four, equipment system level analysis:
View 6509 hardware status with the following status description:
VTT 2:
VTT 2 Ok:not OK
VTT 2 outlettemperature:29c
Description VTT2 module System detection status is not normal
VTT: Voltage terminal module, for Catalyst switching bus. If the redundant Supervisor engine is not installed and the VTT module is in a low or severe temperature condition, the system shuts down. There are three voltage regulators (VTT) on the back panel. If a VTT module fails, a slight alarm will occur. If two faults occur, a major alarm will occur, and the correct action is to shut down the system
V. Conclusion:
the 6509 chassis backplane,VTT2 voltage terminal module anomalies, and now the system still has 2 blocks VTT Module normal operation, if a piece of VTT Voltage Terminal module Abnormal, will make the system serious alarm, if the situation is serious can cause the whole station 6509 stop working.
a 6509 can withstand only 2 blocks of VTT module exceptions.
This article is from the "Frozen vs watermelon" blog, so be sure to keep this source http://molewan.blog.51cto.com/287340/1891370
Cisco 6509 chassis back red light analysis report