General Wiring Design Scheme reference

Source: Internet
Author: User
Tags floor function range reference backup
Chapter I, Technical solutions

1 Preface

This design is in accordance with the latest national standards of the People's Republic of China: "Building and complex cabling system Engineering Design Code" (gb/t50311-2000) and "building and complex cabling system engineering construction and Acceptance Code" (gb/t50312-2000), and according to ******** Bidding requirements and the distribution of building floors, around the application requirements of ********-new office building, from the importance of the integrated wiring, long-term, scalability and the use of integrated wiring system products features.

As an important news unit of the government, its office environment electronic, office automation application level, will directly affect the news collection, editing, sending, publishing and other work of timeliness, accuracy and confidentiality. Therefore, in the planning and design, we fully consider the Computer Information network system, voice communication systems and intelligent subsystems of the integrated wiring system requirements, and strive to build a comprehensive wiring system into a reliable, open, high bandwidth, scalable, and to meet the future development of the wiring system. In accordance with the principle of ' satisfying user's requirement and the principle of advanced, open and standardization, combined with the particularity of news unit work, we recommend using the Avaya Company's Super 5 copper cable series products and optical cable series products in this design proposal, and Avaya the Super 5 type of solutions for system design. The brand products and solutions are in line with the latest international standards, anti-interference ability, advanced and practical, easy to install, management and maintenance of convenient, higher performance price ratio and so on. At the same time, the scheme gives full consideration to the application and development of the users in the future, and has a great scope of expansion and flexibility.

The scope of the scheme is the scope of the "******** tender Request", the function is mainly to meet the computer network communications, voice communications, the network of weak systems of communication and video transmission, not including the intelligent subsystems (such as Monitoring alarm system, conference system, card system) itself required wiring The wiring of each intelligent subsystem is laid with a special cable. ---http://bianceng.cn (computer science)

The content of the design includes the analysis of the customer requirement of the integrated cabling system, the design of the open wiring system and the service. In the scheme design, the overall structure of the integrated wiring system and the design details of each subsystem are described in detail, including the requirement analysis of the wiring system, the distribution of the circuit, the device selection, the material list and the system inspection. The service discusses the quality assurance of the project and the training and engineering documents that we want to provide. Business bids include photocopies of qualification documents, engineering budgets, company profiles, project cases and project participants.

2. Demand Analysis

2.1 Project Overview

The new office building is located in the city of Hongta West Road. Office Building 5 floors, underground half, building 68.2 meters long, 22.4 meters wide, building area of 5324 square meters. The information Center is located on the 5 floor and is the voice/data centre of the entire building. According to the bidding requirements: the total number of building information points to 500 points, the use of more than 5 types of cabling system, part of the use of optical cable to the table. As the basis of information transmission of the integrated wiring system, the focus of its design is: to center room as the core, the office building of the floor with cable and large log cable and the center of the room into an organic whole, so that the system has a stable and reliable, high-speed rate, standard, open, flexible, applicable, scalable performance characteristics, In order to meet the new office buildings in different forms of application requirements.

2.2 Application Requirements Analysis

As the basis of information transmission of the integrated wiring system, must support the current and future voice, data, video conferencing, control and other high-speed transmission of information requirements, for news collection, editing, transmission, publishing and other series of work towards the information, networking lay the foundation.

Therefore, the comprehensive cabling system construction of ********-office building should be considered as a whole. To build an efficient information network, you must have a complete set of high-quality integrated wiring system! For the needs of users and the nature of this wiring project, we recommend the use of the United States Avaya Systimax SCS structured wiring system. This is a set of broadband integrated digital services network requirements and special design of high-quality wiring system, in line with the Ministry of Telecommunications promulgated the standard "Building communication structured wiring System specification", once pushed into the market immediately received a wide range of global response. Avaya Company's Systimax. SCS is a end-to-end full set of cabling solutions, all products are by the Avaya company exclusive research and development, production, and no one product is produced by other manufacturers OEM, which fully guarantee the integrity of the product performance and excellent matching.

According to the bidding requirements of ******** and building plane drawings, we analyze the current and future applications of intelligence:

1. Overall demand

◇ Meet the backbone 1000Mbps, the level 100Mbps switch to the desktop network transmission requirements;
◇ redundant backup of backbone fiber configuration to meet the future expansion;
◇ meet with the telecommunications and its own private network connection;
◇ The function of information point can be flexibly adjusted with need;
◇ compatible with different manufacturers, different brands of network equipment;

2. Functional Requirements:

The design of the integrated wiring system should be able to meet the following communication needs:
◇ Telephone;
◇ computer network;
◇ have the condition of realizing the network integration of BAS, CAS, OAS, SCS, etc.
◇ have the condition of realizing video transmission;
◇ other signal and data transmission which accords with wiring standard;

3. Performance requirements: Service efficiency, quality of service, network throughput, network response time, data transmission speed, resource utilization, reliability, performance/price ratio;

◇ According to the particularity of this project, the voice points and data points use the same transmission medium, that is, the unified use of Super 5 type 4 pairs of twisted pair cable to realize the need of voice and data mutual backup;
◇ for the network backbone, the data communication medium uses the optical fiber, the voice communication backbone uses the large logarithm cable, the optical cable and the large logarithm cable all leave the quantity;
◇ for other system data transmission, can use Super 5 type twisted pair or special cable;
◇ support the current level of 100M, backbone 1000M network applications, and future expansion needs;

4. Environmental requirements: Mainly geographical distribution, the number of users and their location, the distance between users, the organization characteristics of the user group, there are special restrictions (such as cable and other media cabling whether there is a restricted area) and so on; In this project, the wiring is mainly indoors, and no special restrictions are found during the site investigation.

5. Other subsystems (such as office automation systems, equipment control systems, etc.) on the network system requirements;

6. Design constraints: Comply with other standards, the characteristics of various industries of the network's special requirements, investment in the impact of wiring design.

2.3 Information Point Requirements

According to the requirements of the ******** cabling System-Request for tenders: The voice points and data points of the offices in the building have been given a definite quantity requirement, and the information points are reasonably distributed to the appropriate locations of the rooms according to the tender requirements at design time. We propose to increase the number of 1 dual-port information outlets on the first floor for the future ' one-card consumption management ' and an additional 1 dual-port information outlets for the ' Parking Management system ' at the entrance and exit locations of the underground car park. Detailed information point statistics are shown in the following table:

Table of information points and tables
Serial floor function Description Data point Voice point total floor wiring room notes
1 Floor 2 FD1 FD1 wiring between the two-storey control room
21 Floors, 85.
32 floors, 102.
43 Floors, 105.
The 54-layer MD MD Wiring Room is located in the five-storey room, is not only between the floor wiring, but also between the main wiring.
65 floors, 88.
7 Top Caps 2
8 Total 504

In this scenario, we have a total of 504 information points, of which 168 voice points, 336 data points. Voice points and data points are backed up by each other.

2.4 Wiring between the partition and set

As shown in the table above, in accordance with the number of horizontal information points and the premise of the determination of the length of the building according to the size of the long and information points of the cable is ≤ 90 meters requirements, the wiring between the following configuration:

FD1 floor Wiring Room-located in the second floor of the weak 202 room, responsible for the management of 1, 2, 3 layer of information points;
MD Total Wiring-Located in the 5 Floor center room, responsible for the management of 4, 5, top level information points, and the entire large
The main cable and backbone cables of the building, the MD wiring frame is not only the primary wiring frame, but also the floor distribution frame, is the integrated wiring system of the center.

2.5 Design objectives of the system

Considering the high requirements of the comprehensive wiring system for the one-time construction, in order to ensure the advanced, applicability, stability and reliability of the ********-integrated wiring system, and to meet the requirements of the rapid development of the future computer network, we choose the high quality Avaya wiring products in this planning and design.

Synthesis of the current wiring manufacturers solutions and development trends, we recommend the use of the United States Avaya Super 5 wiring products can be very good to ensure that ******** current and future application needs, easy to network upgrades, to avoid the system in the short term into a backward technology phase-out cycle, to maximize the protection of user investment.

Our Design objectives:

Select Advanced, high-quality integrated wiring products, high performance indicators, good process performance to ensure that the integrated wiring system to meet the requirements of intelligent system applications;

The use of optical fiber as the backbone of the system, redundant configuration, improve the system broadband and prevent electromagnetic interference, to adapt to future development;

Backbone Optical cable can support over 1Gbps of network data transmission rate, level Super 5 cable can support 100Mbps above the network data transmission rate;

Star topology, supporting various forms of network applications;

For the office to provide a full range of application platform, support office network equipment, a variety of editing equipment and security equipment, such as system integration;

Taking the cabinet-type wiring system as the core, the system's reliability and security are improved.

The requirements of the integrated cabling system are considered synthetically, and the transmission channel is provided for the integration of the weak system.

With an open structure, can be compatible with many manufacturers of products, with modular, scalable, user-oriented characteristics;

Can fully meet the present and future needs in the voice, data and video communications, can be voice, data and video communications into one, can be applied to a variety of local area network (LAN), can adapt to the future network structure changes or equipment expansion;

3. System Scheme Design

3.1 Design standards and specifications

The design plan adopted by the standards, the structure of the idea, calculation basis, construction code and acceptance follow the following standards or norms:

1 "iso/iec11801 user building general wiring standard"
2) "eia/tia568a,eia/tia568b"
3 GB/T 50311-2000 construction and building complex cabling system Engineering design Code
4 GB/T 50312-2000 construction and building complex cabling system engineering acceptance Code
5 The design of this program is based on the following product specifications:
6) Avaya Integrated Wiring System "design Guide"
7) Avaya Integrated Wiring System "installation Manual"

Contact Us

The content source of this page is from Internet, which doesn't represent Alibaba Cloud's opinion; products and services mentioned on that page don't have any relationship with Alibaba Cloud. If the content of the page makes you feel confusing, please write us an email, we will handle the problem within 5 days after receiving your email.

If you find any instances of plagiarism from the community, please send an email to: info-contact@alibabacloud.com and provide relevant evidence. A staff member will contact you within 5 working days.

A Free Trial That Lets You Build Big!

Start building with 50+ products and up to 12 months usage for Elastic Compute Service

  • Sales Support

    1 on 1 presale consultation

  • After-Sales Support

    24/7 Technical Support 6 Free Tickets per Quarter Faster Response

  • Alibaba Cloud offers highly flexible support services tailored to meet your exact needs.