Part I.: Field wiring
1. Dial code: Toward the number that end is 0, away from the number that end of the 1,PPM address setting method is to dial the dial to the same number as the System schema table, such as a 1u32 number 77020, then its number is 20, 4 and 16 to 1, the other digits to keep 0 bits.
2. Adjust the baud rate: the baud rate is set to 19200, because the field of UCM24 default is 19200, only when the baud rate of communication is the same time the module is able to communicate, otherwise the PPM module can not connect.
The correct dialing code and settings are as follows:
Part II: Program Settings
The following program is the PPM module setup program, need to brush to the PPM bus in the locomotive inside
00010 on ("Ddc-1af-01-m3:enable COV")
00015 if ("Ddc-1af-01-m3:ui_di". Eq.on) then on ("PAU-2-2-YC") Else Off ("PAU-2-2-YC")
00020 if ("Ddc-1af-01-m3:di1". Eq.on) then on ("Eaf-2-6-er") Else Off ("Eaf-2-6-er")
00030 if ("Ddc-1af-01-m3:di2". Eq.on) then on ("Eaf-2-6-st") Else Off ("eaf-2-6-st")
00040 if ("Ddc-1af-01-m3:di3". Eq.on) then on ("Eaf-2-6-at") Else Off ("Eaf-2-6-at")
00050 if ("Eaf-2-6-c". Eq.on) then on ("Ddc-1af-01-m3:do1") Else Off ("Ddc-1af-01-m3:do1")
00060 Goto 10
Other Notes
DDC-1AF-01-M3 is the name of the PPM module (system name)
Ddc-1af-01-m3:ui_di is the name of the 1u32 UI.
Ddc-1af-01-m3:di1 is the name of 1u32 's di point.
PAU-2-2-YC is the imaginary point we defined in the single Point test point table
Ddc-1af-01-m3:do1 is the 1u32 do point, this do point of the program to note that it is to use a virtual point to control a real point
BA-SIEMENS-PPM Module Commissioning